- 32 -
START RELAY ON The start relay is activated
START RELAY OFF The start relay is deactivated during the start sequence
Hz/V OK IN ###s The voltage and frequency on the genset is OK. When the timer runs out it is allowed to operate the generator breaker.
COOLING DOWN ###s Cooling down period is activated.
COOLING DOWN Cooling down period is activated and infinite. Cooling down timer is set to 0.0 s.
GENSET STOPPING This info is shown when cooling down has finished.
EXT. STOP TIME ###s
Extended stop time. The unit will stop after a pre-programmed time of x.x s. after having received a stop signal.