- 36 -
4.3.3 Stopping
– When in MANUAL mode:
• Switch off the load.
• Switch off circuit breaker Q1.
• Press the STOP button to stop the generator.
– When in AUTO mode:
• Switch off the load.
•If in Island mode, the generator stops the
engine by a stop command (e.g. a remote start/
stop signal or set timer).
•If in AMF mode, the unit will switch back to
mains supply when the mains returns.
Switching back to mains supply is done when
the adjusted "Mains OK delay" has expired.
•If in Load Take Over mode, the unit will
switch back to mains when a stop command is
given (e.g. a remote start/stop signal or set
timer).
– After cooldown, the generator will shut down
automatically.
– Turn starter switch S20 in position O (OFF) to
shut down the voltage supply towards the
Qc2103™ controller.
– Lock all doors to avoid unauthorized access