PROGRAMMING MENU
Selects the function of Input A.
6B – Input A Name
Options:
Input Trip (default) No Flow
Low Pressure Starter Disable
High Pressure Controller
Pump Fault PLC
Low Level Vibration
High Level
Selects a message for the keypad to display when Input A is active.
Always Active (default) A trip can occur at any time when the soft starter is receiving power.
Operating Only A trip can occur while the soft starter is running, stopping or starting.
A trip can only occur while the soft starter is running.
Selects when an input trip can occur.
6D – Input A Trip Delay
Range:
0:00 - 4:00 (minutes:seconds)
0 second
Sets a delay between the input activating and the soft starter tripping.
6E – Input A Initial Delay
Range:
00:00 - 30:00 (minutes:seconds)
0 second
Sets a delay before an input trip can occur. The initial delay is counted from the time a start signal is received.
The state of the input is ignored until the initial delay has elapsed.
6F, 6G, 6H, 6I, 6J – Input B Trip
Parameters 6F~6J configure the operation of Input B, in the same way as parameters 6A~6E configure Input A. Refer to Input A for
details.
• 6F
Input B Function
(
Input Trip (N/O))
• 6G
Input B Name
(
Input Trip)
• 6H
Input B Trip
(
Always Active)
• 6I
Input B Trip Delay
(
0:00)
• 6J
Input B Initial Delay
(
0:00)
Parameters 6K and 6L select the function of Inputs C and D. Refer to parameter 6A for details.
Inputs C and D are only available if the input/output expansion card has been installed.
Motor Set Select
Local/Remote Select
Emergency Run
Starter Disable (N/C)
Off (default)
6M – Remote Reset Logic
Options:
Normally Closed (default)
Normally Open
Selects whether the EMX3's remote reset input (terminals C41, C42) is normally open or normally closed.