PROGRAMMING MENU
6
Inputs
6A
Input A Function
Motor Set Select
6B
Input A Name
Input Trip
6C
Input A Trip
Always Active
6D
Input A Trip Delay
0s
6E
Input A Initial Delay
0s
6F
Input B Function
Input Trip (N/O)
6G
Input B Name
Input Trip
6H
Input B Trip
Always Active
6I
Input B Trip Delay
0s
6J
Input B Initial Delay
0s
7
Outputs
7A
Relay A Function
Main Contactor
7B
Relay A On Delay
0s
7C
Relay A Off Delay
0s
7D
Relay B Function
Run
7E
Relay B On Delay
0s
7F
Relay B Off Delay
0s
7G
Relay C Function
Trip
7H
Relay C On Delay
0s
7I
Relay C Off Delay
0s
7M
Low Current Flag
50%
7N
High Current Flag
100%
7O
Motor Temperature Flag
80%
8
Display
8A
Language
English
8B
F1 Button Action
Auto-Start/Stop Menu
8C
F2 Button Action
None
8D
Display A or kW
Current
8E
User Screen - Top Left
Starter State
8F
User Screen - Top Right
Blank
8G
User Screen - Bottom Left
Hours Run
8H
User Screen - Bottom Right
Analog Input
10.6 Extended Menu
The Extended Menu provides access to all the EMX3's programmable parameters.
Parameter Group
Default Setting
1
Motor Data-1
1A
Motor Full Load Current
Model dependent
1B
Locked Rotor Time
0m:10s
1C
Locked Rotor Current
600%
1D
Motor Service Factor
105%
2
Start/Stop Modes-1
2A
Start Mode
Constant Current
2B
Start Ramp Time
10 s
2C
Initial Current
350%
2D
Current Limit
350%
2E
Adaptive Start Profile
Constant Acceleration
2F
Kickstart Time
0000ms
2G
Kickstart Level
500%
User Manual (710-04840-00M) | 41