EasyManua.ls Logo

AuCom EMX3-1600C - Minimum and Maximum Current Settings

AuCom EMX3-1600C
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
APPENDIX
13.4 Minimum and Maximum Current Settings
The EMX3's minimum and maximum full load current settings depend on the model:
In-line connection
Inside delta connection
Model
Minimum
Maximum
Minimum
Maximum
EMX3-0023B 5 A 23 A 5 A 34 A
EMX3-0043B
9 A
43 A
9 A
64 A
EMX3-0050B
10 A
50 A
10 A
75 A
EMX3-0053B 11 A 53 A 11 A 79 A
EMX3-0076B
15 A
76 A
15 A
114 A
EMX3-0097B 19 A 97 A 19 A 145 A
EMX3-0100B 20 A 100 A 20 A 150 A
EMX3-0105B 21 A 105 A 21 A 157 A
EMX3-0145B 29 A 145 A 29 A 217 A
EMX3-0170B 34 A 170 A 34 A 255 A
EMX3-0200B 40 A 200 A 40 A 300 A
EMX3-0220B 44 A 220 A 44 A 330 A
EMX3-0255B 51 A 255 A 51 A 382 A
EMX3-0255C 51 A 255 A 51 A 382 A
EMX3-0350B 70 A 350 A 70 A 525 A
EMX3-0360C 72 A 360 A 72 A 540 A
EMX3-0380C 76 A 380 A 76 A 570 A
EMX3-0425B 85 A 425 A 85 A 638 A
EMX3-0430C 86 A 430 A 86 A 645 A
EMX3-0500B 100 A 500 A 100 A 750 A
EMX3-0580B 116 A 580 A 116 A 870 A
EMX3-0620C 124 A 620 A 124 A 930 A
EMX3-0650C 130 A 650 A 130 A 975 A
EMX3-0700B 140 A 700 A 140 A 1050 A
EMX3-0790C 158 A 790 A 158 A 1185 A
EMX3-0820B 164 A 820 A 164 A 1230 A
EMX3-0920B 184 A 920 A 184 A 1380 A
EMX3-0930C 186 A 930 A 186 A 1395 A
EMX3-1000B 200 A 1000 A 200 A 1500 A
EMX3-1200C 240 A 1200 A 240 A 1800 A
EMX3-1410C 282 A 1410 A 282 A 2115 A
EMX3-1600C
320 A
1600 A
320 A
2400 A