PROGRAMMING MENU
9D – Locked Rotor Current-2
Range:
400% - 1200% FLC
600%
Sets the locked rotor current of the connected motor, as a percentage of full load current. Set according to the
motor datasheet.
9E – Motor Service Factor-2
Range:
100% - 130% FLC
105%
Sets the secondary motor's service factor.
10 Start/Stop-2
10A – Start Mode-2
Options:
Constant Current (default)
Adaptive Control
Selects the soft start mode.
10B – Start Ramp Time-2
Range:
1 - 180 (seconds)
10 seconds
Sets the total start time for an Adaptive Control start or the ramp time for current ramp starting (from the initial
current to the current limit).
10C – Initial Current-2
Range:
100% - 600%
350%
Sets the initial start current level for current ramp starting, as a percentage of motor full load current. Set so
that the motor begins to accelerate immediately after a start is initiated.
If current ramp starting is not required, set the initial current equal to the current limit.
10D – Current Limit-2
Range:
100% - 600% FLC
350%
Sets the current limit for constant current and current ramp soft starting, as a percentage of motor full load
current.
10E – Adaptive Start Profile-2
Options:
Early Acceleration
Constant Acceleration (default)
Late Acceleration
Selects which profile the EMX3 will use for an Adaptive Control soft start.
10F – Kickstart Time-2
Range:
0 - 2000 (milliseconds)
0000 milliseconds
Sets the kickstart duration. A setting of 0 disables kickstart.
10G – Kickstart Level-2
Range:
100% - 700% FLC
500%
Sets the level of the kickstart current.
10H – Stop Mode-2
Options:
Coast To Stop (default)
TVR Soft Stop
Adaptive Control
Brake
Selects the stop mode.
0:00 - 4:00 (minutes:seconds)
0 second
Sets the stop time.
58 | User Manual (710-04840-00M)