PROGRAMMING MENU
9D Locked Rotor Current-2
Range:
400% - 1200% FLC
Default:
600%
Description:
Sets the locked rotor current of the connected motor, as a percentage of full load current. Set according to the
motor datasheet.
9E Motor Service Factor-2
Range:
100% - 130% FLC
Default:
105%
Description:
Sets the secondary motor's service factor.
10 Start/Stop-2
10A Start Mode-2
Options:
Constant Current (default)
Adaptive Control
Description:
Selects the soft start mode.
10B Start Ramp Time-2
Range:
1 - 180 (seconds)
Default:
10 seconds
Description:
Sets the total start time for an Adaptive Control start or the ramp time for current ramp starting (from the initial
current to the current limit).
10C Initial Current-2
Range:
100% - 600%
Default:
350%
Description:
Sets the initial start current level for current ramp starting, as a percentage of motor full load current. Set so
that the motor begins to accelerate immediately after a start is initiated.
If current ramp starting is not required, set the initial current equal to the current limit.
10D Current Limit-2
Range:
100% - 600% FLC
Default:
350%
Description:
Sets the current limit for constant current and current ramp soft starting, as a percentage of motor full load
current.
10E Adaptive Start Profile-2
Options:
Early Acceleration
Constant Acceleration (default)
Late Acceleration
Description:
Selects which profile the EMX3 will use for an Adaptive Control soft start.
10F Kickstart Time-2
Range:
0 - 2000 (milliseconds)
Default:
0000 milliseconds
Description:
Sets the kickstart duration. A setting of 0 disables kickstart.
10G Kickstart Level-2
Range:
100% - 700% FLC
Default:
500%
Description:
Sets the level of the kickstart current.
10H Stop Mode-2
Options:
Coast To Stop (default)
TVR Soft Stop
Adaptive Control
Brake
Description:
Selects the stop mode.
10I Stop Time-2
Range:
0:00 - 4:00 (minutes:seconds)
Default:
0 second
Description:
Sets the stop time.
58 | User Manual (710-04840-00M)