OPERATION
Start Ramp
Time
(seconds)
Compressor - screw -
unloaded
Constant Current 1 200 350 Coast To Stop n/a
Conveyor - horizontal Constant Current 5 200 400 TVR Soft Stop 10
Conveyor - inclined Constant Current 2 200 450 Coast To Stop n/a
(bucket)
Constant Current 2 200 450 Coast To Stop n/a
Crusher - cone Constant Current 1 200 350 Coast To Stop n/a
Crusher - jaw Constant Current 1 200 450 Coast To Stop n/a
Fan - axial (damped) Constant Current 1 200 350 Coast To Stop n/a
Fan - axial (undamped) Constant Current 1 200 450 Coast To Stop n/a
(damped)
Constant Current 1 200 350 Coast To Stop n/a
Fan - centrifugal
(undamped)
Constant Current 1 200 450 Coast To Stop n/a
Mill - ball Constant Current 1 200 450 Coast To Stop n/a
Mill - hammer Constant Current 1 200 450 Coast To Stop n/a
Pump - bore
(Const. accel.)
3 n/a 500
(Const. decel.)
3
Pump - centrifugal
Adaptive Control
(Const. accel.)
10 n/a 500
Adaptive Control
(Const. decel.)
15
Pump - positive
displacement
Adaptive Control
(Const. accel.)
10 n/a 400
Adaptive Control
(Const. decel.)
10
Pump - submersible
(Const. accel.)
5 n/a 500
(Const. decel.)
5
Saw - bandsaw Constant Current 1 200 450 Coast To Stop n/a
EMX4e User Manual (710-18433-00C) | 47