PROGRAMMABLE PARAMETERS
9.4 Parameter List
Parameter Group
Default Setting
1
Motor Details
1A
Command Source
Digital Input
1B
Motor Full Load Current
Model dependent
1C
Locked Rotor Time
00:10 (mm:ss)
1D
Locked Rotor Current
600%
1E
Motor Service Factor
105%
1F
Reserved
2
Motor Start/Stop
2A
Start Mode
Constant Current
2B
Start Ramp Time
00:10 (mm:ss)
2C
Initial Current
200%
2D
Current Limit
350%
2E
Adaptive Start Profile
Constant Acceleration
2F
Stop Mode
TVR Soft Stop
2G
Stop Time
00:00 (mm:ss)
2H
Adaptive Stop Profile
Constant Deceleration
2I
Adaptive Control Gain
75%
2J
Multi Pump
Single Pump
2K
Start Delay
00:00 (mm:ss)
5
Protection Levels
5A
Current Imbalance
30%
5B
Current Imbalance Delay
00:03 (mm:ss)
5C
Undercurrent
20%
5D
Undercurrent Delay
00:05 (mm:ss)
5E
Overcurrent
400%
5F
Overcurrent Delay
00:00 (mm:ss)
5G
Excess Start Time
00:20 (mm:ss)
5H
Restart Delay
00:10 (mm:ss)
5I
Starts per Hour
0
5J
Phase Sequence
Any Sequence
6
Protection Actions
6A
Auto-Reset Count
0
6B
Auto-Reset Delay
00:05 (mm:ss)
6C
Current Imbalance
Soft Trip and Log
EMX4e User Manual (710-18433-00C) | 53