PROGRAMMABLE PARAMETERS
Coast To Stop
TVR Soft Stop (default)
Adaptive Control
Selects the stop mode.
0:00 - 4:00 (minutes:seconds)
0 second
Sets the time for soft stopping the motor using timed voltage
ramp or Adaptive Control.
If a main contactor is installed, the contactor must remain
closed until the end of the stop time. Use the main contactor
output (33, 34) to control the main contactor.
2H –
Adaptive Stop Profile
Options:
Constant Deceleration (default)
Selects which profile the EMX4e will use for an Adaptive Control
soft stop.
2I –
Adaptive Control Gain
Range:
1% - 200%
75%
Adjusts the performance of Adaptive Control. This setting
affects both starting and stopping control.
Single Pump (default)
Manifold Pump
Adjusts the performance of adaptive control to suit installations
with multiple pumps connected to a common outlet manifold.
0:00 - 60:00 (minutes:seconds)
0 second
Sets a delay after the starter receives a start command, before it
starts the motor.
9.7 5 Protection Levels
5A –
Current Imbalance
Range:
10% - 50%
30%
Sets the trip point for current imbalance protection.
60 | EMX4e User Manual (710-18433-00C)