PROGRAMMABLE PARAMETERS
7J
Input A Name
Options:
Input A Trip (default)
Controller
Low Pressure PLC
High Pressure Vibration Alarm
Pump Fault
Field Trip
Low Level
Interlock Trip
High Level Motor Temperature
No Flow Motor Protection
Starter Disable
Feeder Protection
Custom Message
Description:
Selects a message for the keypad to display when Input A is
active.
The custom message can be loaded via the USB port. Refer to
USB Save & Load
on page 35 for details.
7K
Input B Name
Options:
Input B Trip (default)
Controller
Low Pressure PLC
High Pressure Vibration Alarm
Pump Fault
Field Trip
Low Level Interlock Trip
High Level Motor Temperature
No Flow Motor Protection
Starter Disable
Feeder Protection
Custom Message
Description:
Selects a message for the keypad to display when Input B is
active.
9.10 8 Relay Outputs
8A
Relay A Function
Options:
Off Relay A is not used.
Ready The relay is closed when the starter is in
Ready state.
Run (default) The Run output closes when the soft start
is complete (when the starting current falls
below 120% of the programmed motor full
load current) and remains closed until the
beginning of a stop (either soft stop or
coast to stop).