PROGRAMMABLE PARAMETERS
5I –
Starts per Hour
Range:
0 - 10
0
Sets the maximum number of starts the EMX4e will attempt in a
60 minute period. A setting of 0 disables this protection.
5J –
Phase Sequence
Options:
Any Sequence (default)
Positive Only
Negative Only
Selects which phase sequences the soft starter will allow at a
start. During its pre-start checks, the starter examines the
sequence of the phases at its input terminals and trips if the
actual sequence does not match the selected option.
9.8 6 Protection Action
6A –
Auto-Reset Count
Range:
0 – 5
0
Sets how many times the soft starter will auto-reset, if it
continues to trip.
The reset counter increases by one each time the soft starter
auto-resets, and resets after a successful start.
Setting 6A to zero disables auto-reset.
6B –
Auto-Reset Delay
Range:
0:05 - 15:00 (minutes:seconds)
5 seconds
Sets a delay before the soft starter will auto-reset a trip.
(default)
The soft starter will stop the motor as
selected in parameter 2F
Stop Mode
, then
enter trip state. The trip must be reset
before the starter can restart.
The soft starter will stop the motor as
selected in parameter 2F
Stop Mode
, then
enter trip state. The trip will reset after the
auto-reset delay.
Trip Starter The soft starter will remove power and the
motor will coast to stop. The trip must be
reset before the starter can restart.
62 | EMX4e User Manual (710-18433-00C)