PROGRAMMABLE PARAMETERS
The soft starter will remove power and the
motor will coast to stop. The trip will reset
after the auto-reset delay.
The protection will be written to the event
log and the display will show a warning
message, but the soft starter will continue
to operate.
The protection will be written to the event
log but the soft starter will continue to
operate.
Trip + Shunt Relay The soft starter will remove power and the
motor will coast to stop. The shunt trip
relay (33, 34) will activate and the circuit
breaker will disconnect mains voltage from
the soft starter. The circuit breaker must
be manually reset before operation can
resume.
This option is only effective if parameter
20G
Shunt Trip Mode
is set to 'Enable'.
Selects the soft starter's response to each protection. All
protection events are written to the event log.
Soft Trip and Log (default) Warn and Log
Soft Trip and Reset Log Only
Selects the soft starter's response to the protection event.
Soft Trip and Log (default)
Trip Starter Trip + Shunt Relay
Trip and Reset
Selects the soft starter's response to the protection event.
Soft Trip and Log (default) Warn and Log
Soft Trip and Reset Log Only
Selects the soft starter's response to the protection event.
EMX4e User Manual (710-18433-00C) | 63