PROGRAMMABLE PARAMETERS
9.11 9 Analog Output
Current (% FLC)
(default)
Current as a percentage of motor full load
current.
(%)
The motor's temperature, calculated by the
thermal model.
Motor power factor, measured by the soft
starter.
Temperature %
The soft starter's temperature, as a
percentage of the heatsink’s maximum
allowed operating temperature.
Selects which information will be reported via the analog output.
9B –
Analog A Scale
Range:
0-20 mA
4-20 mA (default)
Selects the range of the analog output.
9C –
Analog A Maximum Adjustment
Range:
0% - 600%
100%
Calibrates the upper limit of the analog output to match the
signal measured on an external current measuring device.
9D –
Analog A Minimum Adjustment
Range:
0% - 600%
0%
Calibrates the lower limit of the analog output to match the
signal measured on an external current measuring device.
9.12 10 Display
English (default) Português
Chinese Français
Español Italiano
Deutsch Russian
Selects which language the keypad will use to display messages
and feedback.
10B –
Temperature Scale
Options:
Celsius (default)
Fahrenheit
Selects whether the EMX4e will display temperatures in
degrees Celsius or Fahrenheit.
70 | EMX4e User Manual (710-18433-00C)