PROGRAMMABLE PARAMETERS
7C
Input A Trip Delay
Range:
0:00 - 4:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay between the input activating and the soft starter
tripping.
7D
Input A Initial Delay
Range:
00:00 - 30:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay before an input trip can occur. The initial delay is
counted from the time a start command is received. The state of
the input is ignored until the initial delay has elapsed.
7E
Input B Function
Options:
Input Trip (N/O) (default)
Input Trip (N/C)
Emergency Mode
Description:
Selects the function of Input B. Refer to parameter 7A
Input A
Function
for details.
7F
Input B Trip
Options:
Always Active
Operating Only (default)
Run Only
Description:
Selects when an input trip can occur.
7G
Input B Trip Delay
Range:
0:00 - 4:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay between the input activating and the soft starter
tripping.
7H
Input B Initial Delay
Range:
00:00 - 30:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay before an input trip can occur. The initial delay is
counted from the time a start command is received. The state of
the input is ignored until the initial delay has elapsed.
7I
Reset/Enable Logic
Options:
Normally Closed (default)
Normally Open
Description:
Selects whether the reset input (10, 11) is normally open or
normally closed.
NOTE
If the reset input is active, the starter will not operate.
66 | EMX4e User Manual (710-18433-00C)