Risk of damage to connecting cables and cable glands due to improper install-
ation!
Leakage and ingress of water!
→
If there is need to pull cables for installation: Place lifting accessories like slings
and ropes around the cable or use cable stockings.
→
DO NOT pull at plug/socket connector or cable glands for cable installation or
lifting.
→
Respect minimum bending radii.When installing the connecting cables, make
sure not to fall short of the minimum bending radius.
●
Figure 13: Example: pull cables, correct and wrong
●
Figure 14: Minimum bending radii at plug/socket connector of actuator
Table 10: Minimum bending radii
Minimum bending radius
r [mm]
Outer diameter
(d) [mm]
Connecting cable
90approx. 12.1Motor cable
130approx. 21.7Hybrid cable
●
Exclusively use AUMA “LSW” cable sets as connecting cables1
Table 11: AUMA cable sets
LSW 69LSW 68Cable set
Ready-made
Tested for leak tightness
Ready-made, checked
for leak tightness
Plug/socket con-
nector for actuator
Open connecting cable to wall bracket, wiring to be
performed by the customer
Ready-madePlug/socket con-
nector for wall
bracket
18
SA 07.2-UW – SA 16.2-UW / SAR 07.2-UW – SAR 16.2-UW Control unit: electronic (MWG)
Electrical connection AC 01.2 Non-Intrusive Profinet