EasyManua.ls Logo

AUMA SA-UW - SF Electrical Connection (AUMA Plug;Socket Connector)

AUMA SA-UW
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.3. SF electrical connection (AUMA plug/socket connector)
Figure 16: SF electrical connection
[1] Cover of actuator controls electrical connection (XK) (SF version)
For customer connection of power supply and e.g. to control room
[2] Socket carrier with screw-type terminals
[1]* Cover of wall bracket plug socket connector (XM) (S version)
The plug/socket connector of LSW 68 cable set is readily assembled (wired)
For LSW 69 cable set, the plug/socket connector must be opened and the
cables must be connected to the pin carrier.
[2]* Pin carrier with crimp-type connection
Short description
Plug-in electrical connection with screw-type terminals for power and control contacts.
Control contacts also available as crimp-type connection as an option.
SF version. For power and control cable connection, remove the AUMA plug/socket
connector and the socket carrier from terminal compartment. Removing the cover
is sufficient for connecting the fieldbus cables.
Technical data
Table 13:
Electrical connection via AUMA plug/socket connector
Control contactsPower contacts
50 pins/sockets6 (3 equipped) + protective
earth conductor (PE)
No. of contacts max.
1 to 50U1, V1, W1, U2, V2, W2, PEDesignation
250 V750 VConnection voltage max.
16 A25 ARated current max.
Screw connection, crimp-type (option)Screw connectionType of customer connection
2.5 mm
2
(flexible or solid)
6 mm
2
(flexible)
10 mm
2
(solid)
Connection diameter max.
20
SA 07.2-UW SA 16.2-UW / SAR 07.2-UW SAR 16.2-UW Control unit: electronic (MWG)