Not ready REMOTE (S0006)
The S0006 display shows indications of the Not ready REMOTE group.
If such an indication has occurred, the display shows S0006:
the number of indications occurred
a blinking crossbar after approx. 3 seconds
Figure 48: Not ready REMOTE indications
For further information, please also refer to <Corrective action>.
Fault (S0007)
If a fault has occurred, the display shows S0007:
the number of faults occurred
a blinking exclamation mark after approx. 3 seconds
Figure 49: Fault
For further information, please also refer to <Corrective action>.
7.2.3. Status indications according to NAMUR recommendation
These indications are available, if the parameter Diagnostic classific. M0539 is set
to NAMUR.
Out of Specification (S0008)
The S0008 indication shows out of specification indications according to NAMUR
recommendation NE 107.
If such an indication has occurred, the display shows S0008:
the number of indications occurred
a blinking triangle with question mark after approx. 3 seconds
Figure 50: Out of specification
For further information, please also refer to <Corrective action>.
Function check (S0009)
The S0009 indication shows function check indications according to NAMUR
recommendation NE 107.
If an indication has occurred via the function check, the display shows S0009:
the number of indications occurred
a blinking triangle with a spanner after approx. 3 seconds
40