5.3.4. Fieldbus terminal compartment: open
Figure 21: Open cover to fieldbus terminal compartment
[1] Cover (fieldbus terminal compartment)
[2] Screws for cover
[3] O-ring
[4] Cable entries for fieldbus cables
[5] Blanking plug
Electric shock due to presence of hazardous voltage!
Failure to observe this warning results in death or serious injury.
Disconnect device from the mains before opening.
Electrostatic discharge ESD!
Risk of damage to electronic components.
Earth both operators and devices.
1. Loosen screws [2] and remove cover [1].
2. Insert cable glands suitable for fieldbus cables.
The enclosure protection IP stated on the name plate is only ensured if suit-
able cable glands are used.
Figure 22: Example: Name plate for enclosure protection IP68
3. Seal unused cable entries with suitable plugs.
24
SA 07.2-UW SA 16.2-UW / SAR 07.2-UW SAR 16.2-UW Control unit: electronic (MWG)