EasyManua.ls Logo

AUMA SA-UW - Technical Data Actuator Controls

AUMA SA-UW
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service conditions
For continuous underwater use as well as indoor and outdoor use.Use
Increased enclosure protection IP68-C15.The maximum head of water is 15 m.
Higher heads of water available on request
Enclosure protection according to
EN 60529
Any positionMounting position
2 000 m above sea level
> 2,000 m above sea level on request
Installation altitude
30 °C to +70 °CAmbient temperature
Up to 100 % relative humidity across the entire permissible temperature rangeHumidity
Pollution degree 4 (when closed), pollution degree 2 (internal)Pollution degree according to IEC
60664-1
2 g, from 10 to 200 Hz (for actuators in AUMA NORM version)
1 g, from 10 to 200 Hz (for actuators with mounted AUMA actuator controls)
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Indications apply to actuators with AUMA 3-phase AC motor and AUMA plug/socket
connector.They are not valid in combination with gearboxes.
Vibration resistance according to
IEC 60068-2-6
KX-G: Suitable for use in freshwater (Im1), seawater (Im2) and on seafloor (Im3), aluminium-free version
(outer parts)
Corrosion protection
Two-layer powder coating with additional wet paintingCoating
AUMA silver-grey (similar to RAL 7037)Standard:Colour
Available colours on requestOption:
AUMA multi-turn actuators meet or exceed the lifetime requirements of EN 15714-2. Detailed information
can be provided on request.
Lifetime
< 72 dB (A)Noise level
Further information
Machinery Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
RED Directive 2014/53/EU
EU Directives
12.2. Technical data Actuator controls
Features and functions
Refer to name plate
Permissible variation of mains voltage: ±10 %
Permissible variation of mains voltage: ±30 % (optional)
Permissible variation of mains frequency: ±5 %
Power supply
24 V DC +20 %/15 %
Current consumption: Basic version approx. 250 mA, with options up to 500 mA
For external electronics supply, the power supply of integral controls must have an enhanced isolation
against mains voltage in compliance with IEC 61010-1 and the output power be limited to 150 VA.
External supply of the electronics
(option)
Current consumption of the actuator controls depending on mains voltage:
For permissible variation of mains voltage of ±10 %:
100 to 120 V AC = max. 740 mA
208 to 240 V AC = max. 400 mA
380 to 500 V AC = max. 250 mA
515 V AC = max. 200 mA
Current consumption
Category III according to IEC 60364-4-443Overvoltage category
The actuator controls are designed for the nominal motor power, refer to motor name plateRated power
Via Profinet interfaceControl and feedback signals
60
SA 07.2-UW SA 16.2-UW / SAR 07.2-UW SAR 16.2-UW Control unit: electronic (MWG)
Technical data AC 01.2 Non-Intrusive Profinet

Table of Contents

Other manuals for AUMA SA-UW

Related product manuals