9.3. Limit switching: set
Valve damage at valve/gearbox due to incorrect setting!
Allow for overrun when selecting limit seating.
Prior to setting the limit switching, set the torque switching to the lowest possible
value to avoid valve damage when approaching the end positions.
Customer settings M0041
Limit switching M0010
Set end pos.CLOSED? M0084
Set end pos. OPEN? M0085
Select main menu
1. Set selector switch to position 0 (OFF).
2. Press push button C and hold it down for approx. 3 seconds.
Display goes to main menu and indicates: Display
Select parameter
3. Select parameter either:
click via the menu to parameter, or
via direct display: press and enter ID M0084.
Display indicates: Set end pos.CLOSED?
CLOSED or OPEN
4.
Select via Up Down :
Set end pos.CLOSED? M0084
Set end pos. OPEN? M0085
The black triangle indicates the current selection.
5.
Press Ok.
The display indicates either:
-
Set end pos.CLOSED? CMD0009 continue with step 9
-
Set end pos. OPEN? CMD0010 continue with step 12
-
Specialist (4) continue with step 6
User login
6.
Use Up Down to select user:
Information: Required user level: Specialist (4) or higher
The symbols have the following meaning:
-
black triangle: = current setting
-
white triangle: = selection (not saved yet)
7.
Press Ok to confirm selected user.
Display indicates: Password 0***
8.
Enter password ( enter password).
The display indicates either:
-
Set end pos.CLOSED? CMD0009 continue with step 9
-
Set end pos. OPEN? CMD0010 continue with step 12
48
SA 07.2-UW SA 16.2-UW / SAR 07.2-UW SAR 16.2-UW Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.2 Non-Intrusive Profinet