6.
Press Edit.
➥
Display indicates: ▶ Specialist (4)
User login
7.
Use Up ▲ Down ▼ to select user:
Information: Required user level: Specialist (4) or higher
➥
The symbols have the following meaning:
-
black triangle: ▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
8.
Press Ok.
➥
Display indicates: Password 0***
9.
Enter password (→ enter password).
➥
The screen indicates the pre-set type of seating (▶Limit or ▶Torque) by means
of a black triangle ▶.
Change settings
10.
Use Up ▲ Down ▼ to select new setting.
➥
The symbols have the following meaning:
-
black triangle: ▶ = current setting
-
white triangle: ▷ = selection (not saved yet)
11.
Confirm selection via Save.
➥
The setting for the type of seating is complete.
12.
Back to step 4 (CLOSED or OPEN): Press Esc.
9.2. Torque switching: set
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve).
Valve damage due to excessive tripping torque limit setting!
→
The tripping torque must suit the valve.
→
Only change the setting with the consent of the valve manufacturer.
Customer settings M0041
Torque switching M0013
Trip torque CLOSE M0088
Trip torque OPEN M0089
Default value: According to order data
Setting range: Torque range according to actuator name plate
Select main menu
1. Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates: ▶ Display
Select parameter
3. Select parameter either:
→
click via the menu to parameter, or
→
via direct display: press and enter ID M0088.
➥
Display indicates: Trip torque CLOSE
46
SA 07.2-UW – SA 16.2-UW / SAR 07.2-UW – SAR 16.2-UW Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.2 Non-Intrusive Profinet