Figure 24: Profinet connection board with RJ-45 connections
n1 Profinet cable from previous device
n+1 Profinet cable to next device
(For line topology or redundant ring/MRP - Media Redundancy Protocol)
Profinet connection is made via RJ-45 ports by means of connectors for field
assembly.The scope of delivery includes one RJ-45 Profinet connector for Cat.5
(supplied within electrical connector). Further connectors are available with AUMA
(e.g. for line topology or redundant ring) on request.
Order designations:
RJ-45 Profinet connector for Cat.5 (as included in scope of delivery): AUMA
article number K009.706
Option: RJ-45 Profinet connector for Cat.6
A
cables: AUMA article number
K009.705
Table 17:
Assignment of RJ-45 Profinet port
PinColour of wire insula-
tion
FunctionSignal
1YellowTransmit Data +TD +
2OrangeTransmit Data TD
3WhiteReceive Data +RD +
6BlueReceive Data RD
Description of LEDs on connection board
Table 18:
ExplanationStatusMODS (Module Status)
No voltage or module in SETUP or NW_INIT
status
Not InitialisedRed LED: off +
Green LED: off
The module has aborted NW_INIT statusNormal OperationGreen LED: illuminated
Diagnostic events availableDiagnostic EventsGreen LED: 1 brief pulse
Device in EXCEPTION statusException ErrorRed LED: illuminated +
Red NETS LED: off
Internal device errorFatal EventRed LED: illuminated +
Red NETS LED: illuminated
Do not cut power supply!Firmware updateGreen/Red LEDs:
Alternately blinking
26
SA 07.2-UW SA 16.2-UW / SAR 07.2-UW SAR 16.2-UW Control unit: electronic (MWG)