Page 28
Tone 7 - DIN tone 1200-500
High volume: 90 dB(A) @ 1 m max. / 77 dB(A) @ 1 m min.
Horizontal plane dB(A) @ 1 m
Vertical plane dB(A) @ 1 m
Low volume: 82 dB(A) @ 1 m max. / 70 dB(A) @ 1 m min.
Horizontal plane dB(A) @ 1 m
Vertical plane dB(A) @ 1 m
4.5 Integrated VAD
The following table provides an overview of the VAD intensity and
current consumption for each VAD intensity for white and red LED
indicators.
Technical specifications INTEGRATED VAD
Current
Consumption VAD
(LED indicator not
included)
Current
Consumption
alarm
indicator
At a given mounting height, the
Coverage Volume of a VAD is
defined by the diameter of the
coverage, given in meters.
Example:
C-3-12 corresponds to a ceiling-
mounted device giving a
coverage cylindrical volume of
12 m at 3 m height. For a white
VAD, high intensity is to be
configured.
Open Class: O-2,5-4
(specified at 2,5m height)
Open Class: O-2,5-4
(specified at 2,5m height)
*Available for V-430 only.