Planning
Technical Handbook, AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339, Revision 1, 2020-06-29,
Autronica Fire and Security
Page 42
8.3 Area Coverage and Monitoring Distance
Requirements for both area of coverage and monitoring distance
must be met. Chapter 8.3.1 and 8.3.2 are guidance only (Norwegian
standards).
Local requirements, regulations and laws apply.
8.3.1 Smoke Detection
Note that independent of Operation Class (Smoke only or Multi), the
guidance for smoke detection will apply.
Ceiling height
Area of coverage
Monitoring
distance
Under 6
meters
80 m
2
7,5 meters
+6 12
meters
100 m
2
9 meters
Over 12
meters
See NS-3960:2013