Startup
Installation and Commissioning Handbook, AutroMaster ISEMS - Integrated Safety and Emergency Management System,
116-P-AMASTER-INSTCOMM/IGB, Rev. C, 2016-05-20, Autronica Fire and Security
Page 70
6.15 BS-100 Addresses
To configure the BS-100 address and the serial line to which it is
connected, click and hold down the left mouse button on one of the
designated addresses to BS-100.
This configures a line address for all the BS-100 fire alarm control
panels connected to AutroMaster ISEMS. Control panels that are not
in use are marked "unused".
Defining control panel addresses connected to AutroMaster.
Selection
Serial port and corresponding BS-100
address
ttyS0
Serial port A is connected to the selected BS-
100 address
ttyS1
Serial port B is connected to the selected BS-
100 address
Unused
No serial port is connected to the selected
BS-100 address
Note: This menu is dynamic and the current serial ports are the serial
port addresses defined as BS-100 in 6.13.