Uninterruptible Power Supply (UPS)
Avid highly recommends you create a separate derived power system for your Avid NEXIS. This provides
protection against sudden power surges or losses that could cause you to lose files or experience data
corruption. The power outlets must be served by the same distribution panel. This helps prevent ground loops
that can be caused by plugging equipment into power sources with different ground potentials.
See “Power Supplies” on page 18 for more information, and provide a UPS that meets the power
requirements of each individual power supply module in the Engines in your environment. Make sure there is
adequate, dedicated power for each UPS.
w
Make sure all the electrical work at your site is done by a licensed electrician. The electrical changes
must meet country, state, and local electrical codes.
Component EMC Safety
Avid NEXIS | SDA FCC pt15B Class A, EN55022 Class A,
CISPR 22 Class A, EN 55024, CISPR24,
EN61000-3-2/3, CNS13438
EN/IEC/UL 60950-1, CNS14336 CB report: CE, UL,
cUL, FCC, BSMI, VCCI, CCC (PSU only)
Avid NEXIS | PRO FCC pt15B Class A, EN55022 Class A,
CISPR 22 Class A, EN 55024, CISPR24,
EN61000-3-2/3, CNS13438
EN/IEC/UL 60950-1, CNS14336 CB report: CE, UL,
cUL, FCC, BSMI, VCCI, CCC (PSU only)
Avid NEXIS | E2
Avid NEXIS | E2 SSD
FCC pt15B Class A, EN55022 Class A,
CISPR 22 Class A, EN 55024, CISPR24,
EN61000-3-2/3, CNS13438
EN/IEC/UL 60950-1, CNS14336 CB report: CE, UL,
cUL, FCC, BSMI, VCCI, CCC (PSU only)
Avid NEXIS | E4 FCC pt15B Class A, EN55022 Class A,
CISPR 22 Class A, EN 55024, CISPR24,
EN61000-3-2/3, CNS13438
EN/IEC/UL 60950-1, CNS14336 CB report: CE, UL,
cUL, FCC, BSMI, VCCI, CCC (PSU only)
Avid NEXIS | E5 FCC pt15B Class A, EN55022 Class A,
CISPR 22 Class A, EN 55024, CISPR24,
EN61000-3-2/3, CNS13438
EN/IEC/UL 60950-1, CNS14336 CB report: CE, UL,
cUL, FCC, BSMI, VCCI, CCC (PSU only)