D-7
Display Item Contents
Initial value
Setting value
Key operation • display
C75
MV display setup 
(Sum of the weighting)
Bit 0: MV display (Enabled: +1) 
Bit 1: Heat MV/cool MV display (Enabled: +2) 
Bit 2: MFB display (Enabled: +4) 
Bit 3: AT progress display (Enabled: +8)
15
C76
Event setting value display 
setup (Operation display)
0: Not displayed 
1: Set value of Internal event 1 is displayed 
2: Set values of Internal event 1 to 2 are displayed 
3: Set values of Internal event 1 to 3 are displayed
0
C77
Event remaining time display setup 
(Operation display)
0: Not displayed   1: Internal event 1 is displayed 
2: Internal event 1 to 2 is displayed 
3: Internal event 1 to 3 is displayed
0
C78
CT input current value display setup 
(Operation display)
0: Not displayed  1: CT1 current value is displayed 
2: CT1 to 2 current values are displayed
0
C79
User level 0: Simple configuration  1: Standard configuration 
2: High function configuration
1
C80
LED monitor 0: Not used 
1: 
Flashing while data is sending through RS-485 communication. 
2: 
Flashing while data is receiving through RS-485 communication.
 
3: 
Logical OR of all DI statuses
   4: 
Flashing in READY mode
0
C8
 
1
MS indicating lamp ON condi-
tion (1st priority)
0: Normally OFF   1: Normally ON   2 to 9: Internal event 1 to 8 
10 to 13: Undefined   14: MV1   15: MV2   16 to 17: Undefined 
18 to 21: DI1 to 4   22 to 25: Undefined    
26 to 30: Internal contact 1 to 5   31 to 33: Undefined  
34 to 37: Communication DI 1 to 4   38: MANUAL   39: READY 
40: RSP   41: AT   42: During ramp   43: Undefined   44: Alarm 
45: PV alarm   46: Undefined   47: [mode] key pressing status 
48:
 
Event output 1 terminal status   
49: 
Control output 1 terminal status
39
C82
MS indicating lamp ON status 
(1st priority)
0: lit  1: Slow flashing   2: Flashing twice    
3: Fast flashing   4: Left to right   5: Right to left    
6: 
Reciprocating between left and right   
7: 
Deviation OK 
8: 
Deviation graph   
9: 
MV graph   
10: 
Heat-side MV graph 
11: 
Cool-side MV graph   
12: 
MFB graph  
 13: 
DI monitor
 
14: 
Internal contact monitor   
15: 
Internal event monitor
1
C83
MS indicating lamp ON condi-
tion (2nd priority)
Same as MS display, Condition (1st priority) 44
C84
MS indicating lamp ON status 
(2nd priority)
Same as MS display, Status (1st priority) 6
C85
MS indicating lamp ON condi-
tion (3rd priority)
Same as MS display, Condition (1st priority) 1
C86
MS indicating lamp ON status 
(3rd priority)
Same as MS display, Status (1st priority) 9
C87
MS indicating lamp deviation range
0 to 9999U  5
C88
Special function 
0 to 15 (This value becomes "0" when the power is turned ON.)
0
C89
Zener barrier adjustment
The value can be changed with the adjustment.  The numeric 
value cannot be directly input with the manual operation.
0.00
C90
Number of CT1 turns 0: 800 turns   1 to 40: CT turns divided by 100 8
C9
 
1
Number of CT1 power wire loops
0: 1 time   1 to 6: Number of times 1
C92
Number of CT2 turns 0: 800 turns   1 to 40: CT turns divided by 100 8
C93
Number of CT2 power wire loops
0: 1 time   1 to 6: Number of times 1
C97
PV input failure (under range) 
type *
1
0: 10 %FS 
1:  5 mV
 (This setting is applicable if C01 (PV input range 
type) is set for sensor type B (No.17) or PR40-20 (No. 23))
0
*1  Cannot be selected if ROM version 1 ( 
i
 
d02
) of the instrument information bank is 2.26 or earlier.
EvCF
  [Event configuration bank]
Display Item Contents
Initial value
Setting value
E
 
1.C
 
1
 to 
E8.C
 
1
Internal event 1 to 8 Configuration 1
Refer to event type (see page 8) 0
E
 
1.C2
 to 
E8.C2
Internal event 1 to 8 Configuration 2
The digits are determined to 1st, 2nd, 3rd, and 
4th digit from the right end.
1st digit: Direct/Reverse 0: Direct   1: Reverse 0
2nd digit: Standby 0: None  1: Standby  2: 
Standby + Standby at SP change
0
3rd digit: 
EVENT state at READY
0: Continue   1: Forced OFF 0
4th digit: Undefined 0 0
E
 
1.C3
 to 
E8.C3
Internal event 1 to 8 Configuration 3
The digits are determined to 1st, 2nd, 3rd, and 
4th digit from the right end.
1st digit: Alarm OR 0: None   1: Alarm direct + OR operation    
2: Alarm direct + AND operation    
3: Alarm reverse + OR operation 
4: Alarm reverse + AND operation
0
2nd digit: Special OFF 0: As usual 
1:  
When the event set value (main setting) is 0, the event is "OFF".
0
3rd digit: Delay time unit 0: 0.1s   1: 1s   2: 1min 0
4th digit: Undefined 0 0
di
  [DI assignment bank]
Display Item Contents
Initial value
Setting value
dI
 
1
. 
1
 to 
dI
 
5.
 
1
Internal contact 1 to 5 
Operation type
0: No function   1: LSP group selection (0/+1) 
2: 
LSP group selection (0/+2)   
3: 
LSP group selection (0/+4)
 
4: 
PID group selection (0/+1)   
5: 
PID group selection (0/+2) 
6: 
PID group selection (0/+4)   
7: 
RUN/READY selection 
8: 
AUTO/MANUAL selection   
9: 
LSP/RSP selection    
10: 
AT Stop/Start   
11: 
Invalid   
12: 
Control action direct/reverse 
13: SP Ramp enabled/disabled   14: PV Hold    
15: 
PV Maximum value hold
   16: 
PV Minimum value hold    
17: 
Timer Stop/Start   
18: 
Release all DO latches (Continue/Release)
 
19: Advance   20: Step hold
0
dI
 
1.2
 to 
dI
 
5.2
Internal contact 1 to 5 
Input bit operation
0: 
Not used (Default input)   
1: 
Function 1 ((A and B) or (C and D)) 
2: 
Function 2 ((A or B) and (C or D))
 
3: 
Function 3 (A or B or C or D)
 
4: 
Function 4 (A and B and C and D)
0
dI
 
1.3
 to 
dI
 
5.3
Internal contact 1 to 5 
Input assignment A
0: Normally opened   1: Normally closed   2: DI1   3: DI2   
4: DI3   5: DI4   6 to 9: Undefined    
10 to 17: Internal event 1to 8 
18 to 21:
 
Communication DI1 to 4   
22:
 
MANUAL   23: READY
 
24: RSP   25: AT running   26: During SP ramp  
27: Undefined   28: Alarm occurs   29: PV alarm occurs  
30: Undefined   
31: mode key pressing status    
32: Event output 1 status
   33: Control output 1 status
2 to 5 
or 0
dI
 
1.4
 to 
dI
 
5.4
Internal contact 1 to 5 
Input assignment B
0
dI
 
1.5
 to 
dI
 
5.5
Internal contact 1 to 5 
Input assignment C
0
dI
 
1.6
 to 
dI
 
5.6
Internal contact 1 to 5 
Input assignment D
0
dI
 
1.7
 to 
dI
 
5.7
Internal contact 1 to 5 
Polarity A to D
The digits are determined to 1st, 2nd, 3rd and 
4th digit from the right end.
1st digit: Polarity A 0: Direct   1: Reverse 0
2nd digit: Polarity B 0
3rd digit: Polarity C 0
4th digit: Polarity D 0
dI
 
1.8
 to 
dI
 
5.8
Internal contact 1 to 5 Polarity 0: Direct   1: Reverse
0
dI
 
1.9
 to 
dI
 
5.9
Internal contact 1 to 5 
Internal event No. assignment
0: Every Internal Event 
1 to 8: Internal Event No.
0
dO
  [DO assignment bank]
Display Item Contents
Initial value
Setting value
Ot
 
1.
 
1
 to 
Ot2.
 
1�
Ev
 
1.
 
1
 to 
Ev3.
 
1
Control output 1 to 2, event 
output 1 to 3 Operation type
0: Default output   1 to 2: MV1 to 2 
3 to 6: Function 1 to 4
0
Ot
 
1.2
 to 
Ot2.2�
Ev
 
1.2
 to 
Ev3.2
Control output 1 to 2, event 
output 1 to 3 Output assign-
ment A
0: Normally opened   1: Normally closed 
2 to 9: Internal Event 1 to 8   10 to 13: Undefined 
14 to 15: MV1 to 2   16 to 17: Undefined    
18 to 21: DI1 to 4   22 to 25: Undefined    
26 to 30: Internal Contact 1 to 5 
31 to 33:
 Undefined   
34 to 37:
 DI1 to 4   
38:
 MANUAL 
39: READY   40: RSP mode   41: AT running    
42: During SP ramp   43: Undefined    
44: Alarm occurs   45: PV alarm occurs    
46: Undefined   47: Mode key pressing status 
48:
 Event output 1 status   
49:
 Control output 1 status
14: 
Output 1 
15: 
Output 2 
2: Event 1 
3: Event 2 
4: Event 3
Ot
 
1.3
 to 
Ot2.3�
Ev
 
1.3
 to 
Ev3.3
Control output 1 to 2, event output 
1 to 3 Output assignment B
0
Ot
 
1.4
 to 
Ot2.4�
Ev
 
1.4
 to 
Ev3.4
Control output 1 to 2, event output 
1 to 3 Output assignment C
0
Ot
 
1.5
 to 
Ot2.5�
Ev
 
1.5
 to 
Ev3.5
Control output 1 to 2, event output 
1 to 3 Output assignment D
0
Ot
 
1.6
 to 
Ot2.6�
Ev
 
1.6
 to 
Ev3.6
Control output 1 to 2, event 
output 1 to 3 Polarity A to D
The digits are determined to 1st, 2nd, 3rd, and  
4 th digit from the right end.
1st digit: Polarity A 0: Direct 
1: Reverse
0
2nd digit: Polarity B 0
3rd digit: Polarity C 0
4the digit: Polarity D 0
Ot
 
1.7
 to 
Ot2.7�
Ev
 
1.7
 to 
Ev3.7
Control output 1 to 2, event 
output 1 to 3 Polarity
0: Direct 
1: Reverse
0
Ot
 
1.8
 to 
Ot2.8�
Ev
 
1.8
 to 
Ev3.8
Control output 1 to 2, event 
output 1 to 3 Latch
0: None   1: Latch (Latch at ON) 
2:  
Latch (Latch at OFF except for initialization at power ON)
0
UF
  [User function bank]
Display Item Contents
Initial value
Setting value
UF-
 
1
 to 
UF-8
User function 1 to 8  
LOC
  [Lock bank]
Display Item Contents
Initial value
Setting value
LOC
Key lock 0: All settings are possible 
1:  Mode, event, operation display, SP, UF, lock, 
manual MV can be set
2:  
Operation display, SP, UF, lock, manual MV can be set
3: UF, lock, manual MV can be set
0
C.LOC
Communication lock 0: read/write enabled   1: read/write disabled 0
L.LOC
Loader lock 0: read/write enabled   1: read/write disabled 0
PASS
Password display 0 to 15 (5: Password 1A to 2B display) 0
PS
 
1A
Password 1A 0000 to FFFF (Hexadecimal value) 0000
PS2A
Password 2A 0000 to FFFF (Hexadecimal value) 0000
PS
 
1b
Password 1B 0000 to FFFF (Hexadecimal value) 0000
PS2b
Password 2B 0000 to FFFF (Hexadecimal value) 0000
I
 
d
  [Instrument information bank]
Display Item Contents
Initial value
Setting value
I
 
d0
 
1
ROM ID 2: Fixed 0
I
 
d02
ROM Version 1 XX. XX (2 digits after decimal point) 
I
 
d03
ROM Version 2 XX. XX (2 digits after decimal point) 
I
 
d04
Loader information 
I
 
d05
EST information 
I
 
d06
Manufacturing date code 
(year)
Subtract 2000 from the year. 
Example: "3" means the year 2003.
I
 
d07
Manufacturing date code 
(month, day)
Month + day divided by 100. 
Example: "12.01" means the 1st day of December.
I
 
d08
Serial No. 
  Precaution for setup
•  The type of auto tuning can be changed by changing the value of 
At.ty
 (AT type) in the extended tuning bank. Set it to match the 
control characteristics.
•  Make sure that the motor will be adjusted. Set 
C60
 (Motor auto 
adjust) in [Setup bank] to “1” (Start). 
•  For position proportional control models, derivative time (D) will 
be 0 seconds when AT is complete. If satisfactory control results 
cannot be obtained, set 
At-d
 (AT derivative time adjust) in 
[Extended tuning bank] to “1.00.”
Memo
Changing the user level
This controller's user level can be set to 1 of 3 types in setup 
C79
.
The number of possible displays and settings decreases according 
to the user level: high function > standard > simple. All items are 
displayed when high function is selected.
1
Press [display] once 
to get the operation 
display. 
Next, press and hold 
[para] for more than 2s 
to get the parameter 
setup display.  
MOde
 
flashes on the upper 
display.
2
Press [ ] or [ ] repeat-
edly as needed to get 
STUP
 flashing on the 
upper display.
3
Press [enter]. 
C0
 
1
 is shown on the 
upper display. 
Press [<], [ ] or [ ] to 
change to 
c79
 (user 
level).
4
When [enter] is 
pressed, the lower  
display flashes. 
Press [
] or [ ] to 
change to the desired 
setting, and press 
[enter] to finalize your 
selection.
0:  Simple configuration 
1:  Standard configuration 
(initial value)
2: 
High function configuration
• Items marked 
 in the tables are displayed in standard and/or high function configuration.
• To change a user level, refer to 
Changing the user level
 in the lower right part of this page.