13-2
Chapter 13.  SPECIFICATIONS
 Resistance temperature detector (RTD) input
Input bias current: Approx. +1 mA (flows from terminal A.)
Burnout indication:
RTD burnout or A-wire burnout .......Upscale + AL01 
B-wire burnout or C-wire burnout ....Upscale + AL01, AL03 
2 or more wires burnout ...................Upscale + AL01, AL03
Effect of wiring 
resistance:
 
Max. ±0.05 %FS/Ω
Allowable wiring 
resistance:
 
10 Ω or less for range No. 53 to 62 (Zener barrier cannot be used.) 
85 Ω or less for ranges other than above range (including the resistance of 
the Zener barrier)
Allowable input voltage
: -0.5 to +12 V
 DC voltage input
Input impedance: Min. 1 MΩ
Input bias current:
1 V range or less .............................Max. 1 μA (flows to the (+) terminal) 
0 to 5 V, 1 to 5 V range ....................Max. 3.5 μA (flows to the (+) terminal) 
0 to 10 V range ...............................Max. 7 μA (flows to the (+) terminal)
Burnout indication:
Downscale + AL02 
However, the burnout cannot be detected in a range of 0 to 10V.
Allowable input voltage
:
-0.5 to +12 V
 DC current input
Input impedance: Max. 100 Ω
Burnout indication:
Downscale + AL02 
However, the burnout cannot be detected in a range of 0 to 20 mA.
Allowable input current
: Max. 30 mA
Allowable input voltage
: Max. 4 V (a higher voltage might cause input circuit failure)
* When the power to this controller is turned off, the current input circuit is cut off. If you connect 
two or more current-input type controllers in series, change the current input to voltage input by 
connecting a resistor (No. 81401325, sold separately).  See Chapter 4.
Motor feedback potentiometer input (R1 model)
Allowable resistance: 100 to 2500 Ω
Burnout detection:
AL07 indication
RSP input
Input type: Linear 0 to 20 mA/4 to 20 mA or linear 0 to 5 V/1 to 5 V/0 to 10 V
Scaling: Possible in a range of -1999 to +9999.  It is also possible to set the decimal 
point position.
Sampling cycle: 100 ms
Indication accuracy:
±0.1 %FS±1digit (at an ambient temperature of 23±2 °C)
 Voltage input specifications
Input impedance: Min. 1 MΩ
Input bias current:
0 to 5 V, 1 to 5 V range ........................Max. 3 μA (flows to the (+) terminal) 
0 to 10 V range .....................................Max. 5 μA (flows to the (+) terminal)
Burnout indication: Downscale + AL06
 Current input specifications
Input impedance: Max. 100 Ω
Burnout indication: Downscale + AL06 
However, the burnout cannot be detected in a range of 0 to 20 mA.
Allowable input current
: Max. 30 mA
Allowable input 
voltage
:
Max. 4 V(a higher voltage might cause device failure)