EasyManua.ls Logo

Azbil SDC36 - Resistance temperature detector (RTD) input

Azbil SDC36
290 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13-2
Chapter 13. SPECIFICATIONS
Resistance temperature detector (RTD) input
Input bias current: Approx. +1 mA (flows from terminal A.)
Burnout indication:
RTD burnout or A-wire burnout .......Upscale + AL01
B-wire burnout or C-wire burnout ....Upscale + AL01, AL03
2 or more wires burnout ...................Upscale + AL01, AL03
Effect of wiring
resistance:
Max. ±0.05 %FS/Ω
Allowable wiring
resistance:
10 Ω or less for range No. 53 to 62 (Zener barrier cannot be used.)
85 Ω or less for ranges other than above range (including the resistance of
the Zener barrier)
Allowable input voltage
: -0.5 to +12 V
DC voltage input
Input impedance: Min. 1 MΩ
Input bias current:
1 V range or less .............................Max. 1 μA (flows to the (+) terminal)
0 to 5 V, 1 to 5 V range ....................Max. 3.5 μA (flows to the (+) terminal)
0 to 10 V range ...............................Max. 7 μA (flows to the (+) terminal)
Burnout indication:
Downscale + AL02
However, the burnout cannot be detected in a range of 0 to 10V.
Allowable input voltage
:
-0.5 to +12 V
DC current input
Input impedance: Max. 100 Ω
Burnout indication:
Downscale + AL02
However, the burnout cannot be detected in a range of 0 to 20 mA.
Allowable input current
: Max. 30 mA
Allowable input voltage
: Max. 4 V (a higher voltage might cause input circuit failure)
* When the power to this controller is turned off, the current input circuit is cut off. If you connect
two or more current-input type controllers in series, change the current input to voltage input by
connecting a resistor (No. 81401325, sold separately). See Chapter 4.
Motor feedback potentiometer input (R1 model)
Allowable resistance: 100 to 2500 Ω
Burnout detection:
AL07 indication
RSP input
Input type: Linear 0 to 20 mA/4 to 20 mA or linear 0 to 5 V/1 to 5 V/0 to 10 V
Scaling: Possible in a range of -1999 to +9999. It is also possible to set the decimal
point position.
Sampling cycle: 100 ms
Indication accuracy:
±0.1 %FS±1digit (at an ambient temperature of 23±2 °C)
Voltage input specifications
Input impedance: Min. 1 MΩ
Input bias current:
0 to 5 V, 1 to 5 V range ........................Max. 3 μA (flows to the (+) terminal)
0 to 10 V range .....................................Max. 5 μA (flows to the (+) terminal)
Burnout indication: Downscale + AL06
Current input specifications
Input impedance: Max. 100 Ω
Burnout indication: Downscale + AL06
However, the burnout cannot be detected in a range of 0 to 20 mA.
Allowable input current
: Max. 30 mA
Allowable input
voltage
:
Max. 4 V(a higher voltage might cause device failure)

Table of Contents

Other manuals for Azbil SDC36

Related product manuals