13-5
Chapter 13.  SPECIFICATIONS
 Continuous voltage output
Output type: 0 to 5 V DC, 1 to 5 V DC or 0 to 10 V DC voltage output
Allowable load 
resistance:
 
Min. 1000 Ω
Output accuracy: ±0.1 %FS (at an ambient temperature of 23±2 °C) 
However, ±1 %FS at 0 to 0.05 V.
Output resolution: 1/10000
Event relay output
Number of output 
points:
 
2 to 3 points (This may vary depending on the model.)
Output type: SPST contact 
3 points, 3 points/common; 2 points, Each individual contact
Output rating: 250 V AC/30 V DC, 2 A (resistive load)
Life: 100,000 cycles or more
Min. open/close 
specifications:
 
5 V, 10 mA (Reference value)
RS-485 communication
Transmission line: 3-wire method
Transmission speed: 4800, 9600, 19200, 38400 bps
Communication 
distance:
 
Max. 500 m
Communication 
method:
 
Half duplex, start/stop synchronization method
Communication 
protocol:
 
In conformity with CPL and Modbus
Number of  
connection units:
 
Max. 31 units
Terminating resistor: Connection prohibited.
Loader communication
Transmission line: 3-wire method
Transmission speed: Fixed at 19200 bps.
Recommended cable: Included with the SLP-C35J50.
Isolation between input and output
Portions enclosed by solid lines are insulated from other signals. 
Portions enclosed by dotted lines are not insulated.
Power supply
Internal circuit
Control output 1
PV input Control output 2
CT input 1 Auxiliary output
CT input 2
MFB input
Loader communication
Digital input 1
Digital input 2
Digital input 3
Digital input 4
RS-485 communication
Event output 1 * 
Event output 2 * 
Event output 3
RSP input
The inputs and outputs provided may vary depending upon the model. 
*  In case of the independent contacts, the output 1 and the output 2 are isolated.