CAUTION
The controller requires 6 seconds to stabilize after power ON. Great care should be taken
when the relay output from the controller is used as interlock signals.
The part between the control output 1 and control output 2 is not isolated. When necessary,
use an appropriate isolator.
Do not connect multiple loader cables to multiple units from one personal computer. The
current coming from other circuits might cause the PV value indication error to occur.
Do not connect any terminating resistor in the communication path when performing the
RS-485 wiring.
Doing so might cause the communication to fail.
Do not operate the key with a pencil or sharp-tipped object.
Doing so might cause faulty operation.