1. Overview
ModMAG
®
M2000 supports ModBus
®
RTU communications. Port A (pins 5, 6, 7) support
ModBus
®
RTU using RS232.The RS485 is supported as an accessory daughterboard. Verify
or configure the ModMAG
®
M2000 communication port B. Access the port settings at main
menu > communications > port B settings.
The tables to follow identify the ModBus
®
registers and attributes that exist in the ModMAG
®
M2000 flow meter. Each register has attributes that are also specified in the tables.
Parameter
Value
Comments
Port address
001
Mandatory value of 001
Extended port address
-
Application specific. sets
ModBus
®
address of module
Baud rate
38400
ModBus
®
daughterboard
auto-bauds
Data bits
8
Mandatory value of 8
Parity
EVEN
Mandatory value of EVEN
Stop bits
1
Mandatory value of 1
1.1 Write security
Write security identifies the required security level of the register in order to be suc-
cessfully written. This attribute does not apply to the readability of the register and re-
gisters listed with admin, service or user are unprotected if the meter is not secured
(that is, admin pin is not programmed.)
Firmware - Typically, read-only registers.This means only the flow meter firmware
has the privilege to update the register.
Factory Includes registers that can only be written by the factory
Admin Registers that require admin level access
Service Registers that require service level access
User Registers that require user level access
None Register is always unprotected
All registers can be protected by enabling security on the flow meter. Once the flow
meter is secured, all registers are write-protected unless remote privilege is granted.
All read accesses to registers are still accepted when the flow meter is secured.
Obtaining remote privilege for write operations requires a sequence of ModBus
®
actions to take place. Remote login process is encrypted to ensure protection of the
log-in pins.
Read the random value register (address 0x012B).
Perform necessary calculations (contact Badger Meter for details).
Write the remote login register (address 0x012F).
It is advised that a support application is written to perform this process and embed-
ded within the main application software used to access the flow meter.