Motorized Linear Actuator baelz 373-E07
DIP10:
An actuator characteristic can be used indirectly to change a valve characteristic. If, for
example,thevalvehasanequalpercentagecharacteristic,aninverseequalpercentage
actuator characteristic can be used to generate a resulting linear characteristic, see illustration
below.
The actuator characteristic (DIP 10) can also be combined with the characteristics which
canbeselectedusingDIPs7,8and9(e.g.splitrange).Themicrocontrollerrstprocesses
thecharacteristicdenedbyDIPs7,8and9andsubsequentlythecharacteristicdenedby
DIP 10.
InModbusmode,twofurtheractuatorcharacteristicscanbeselected:equalpercentageand
quadraticinverseequalpercentage.
DIP11:
DIPswitch11denesthemodeofoperation:1=Modbusmode,0=standardmode.
Standardmodeisusedtoapplypredenednormalsettings.
DIP12:
Starts an initialization run when switched from 0 to 1. If DIP 12 is left in position 1 when the
7020 positioner is switched on, an initialization run will not be startet.
As long as DIP 12 is set to 1, errors and alarms occurring during normal positioner operation
will not be shown. This enables errors occurring during initialization to be distinguished from
errors during normal positioner operation. Switch DIP 12 back to 0 after the initialization run
(after having analysed possible error codes) to show any errors occurring in normal positioner
operationontheredLED.Seealsosection7.5.2"Initializationrun".
shut
valve2,o󰀨set50%[010]*
valve1,o󰀨set0%[100]*
valve1,o󰀨set0%[110]*
valve2,o󰀨set33,3%[001]*
valve1,o󰀨set66,6%[101]*
input signal
valve position
open
shut
0% 100%
50%
33,3%
66,6,%
100%
0%
100%
0%
shut
shut
open open
shut
open
open
0% 100%
0% 100%
Split range
split50%
Linear
Split range
split33%
11-point
characteristic
Inverse linear
[000]
[011]* [111]*
Fig. 27: Graphical illustration of selection of functions by DIP switches 7, 8 & 9
1
Desired
characteristic
Equalpercentage
Quadratic
Linear
Equalpercentage
Linear
DIP-switch 10
Characteristic of the
valve
Characteristic of the
actuator
E󰀨ective at valve
=factorysetting
Travel
Travel
Travel
Travel
Travel
Signal
Signal
Signal
Signal
Signal
Signal
Signal
Signal
Signal
Signal
TravelTravelTravelTravel
a
Travel
1
0
10
0
10
1
0
10
actuator characteristic
only selectable in
Modbus mode
actuator characteristic
only selectable in
Modbus mode

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Baelz Automatic 373-E07 and is the answer not in the manual?

Baelz Automatic 373-E07 Specifications

General IconGeneral
BrandBaelz Automatic
Model373-E07
CategoryController
LanguageEnglish

Related product manuals