22 Power Panel User's Manual
Power Panel • Power Panel PP41
Electrical Isolation
Input - PLC
Input - Output
Yes
Yes
Digital Outputs
Amount/Type
Highside Driver IC (Transistor)
Potential-Free Relay Contact
8
1
Switching Voltage
Minimum
Nominal
Maximum
18 VDC
24 VDC
30 VDC
Continuous Current per
Output
Module
Max. 0.4 A
Max. 3.2 A
Load for Potential-Free Relay Contact Max. 0.5 A
Leakage Current when Switched Off 12 µA
Overload Protection Yes
Switching On after Overload Cutoff Automatically within seconds (depends on the panel temperature)
Continuous Short Circuit Current Typ. 4 A
Internal Protective Circuit Yes
Braking Voltage when Switching Off Inductive Loads 47 V
Switching Delay
Log. 0 - Log. 1
Log. 1 - Log. 0
Max. 450 µs
Max. 450 µs
Electrical Isolation
Output - PLC
Output - Input
Yes
Yes
HMI
Display Type LCD B/W
Resolution QVGA (320 x 240 pixels)
Display Diagonal 5.7" (145 mm)
Background Lighting
Brightness
Lifespan
1)
2)
150 cd/m²
20000 h
Reading Angle Approx. 3
Keyboard
Number of Keys
Design
Function Keys
System Keys
40 membrane keys
Covered keypad with metallic snap-action disks
16, with LEDs, labeled with legend sheets
24 (number block, cursor block, control keys)
Front Multi-layered front with insertion slots for key legends
Protection According to IEC 60529 IP65 (from front)
Product ID PP41
Table 6: Technical data for PP41 (cont.)