Sensor positions
threshold midway
between taught conditions
Darkest
(no signal)
Most Light
(saturated
signal)
Output OFF Output ON
Darkest Taught
Condition
Lightest Taught
Condition
Position
adjusted by
Manual
Adjust
Figure 7. Dynamic TEACH (Light Operate shown)
The Output ON and OFF condions can be reversed by using the LO/DO (Light Operate/ Dark Operate) switch or through the program
interface for the dual output model.
Dynamic TEACH and Manual Adjust
Moves switching threshold value up or down to make adjustments
•
Slide Mode switch to ADJ to enter Adjust mode
• Press "+" to increase; press "-" to decrease
◦ GREEN display shows the switching threshold value
◦ 2 seconds aer adjustment, GREEN display will ash 3
mes to conrm
• Slide Mode switch to RUN to complete operaon
Remember: Manual adjustments are disabled when Auto Thresholds are ON
Follow these steps to perform Dynamic TEACH:
Note: TEACH Selecon must be programmed to dYn tcH.
1. Enter Adjust Mode.
Method Acon Result
SET Buon
8
Set Mode switch to ADJ Display: Red - Signal Level; Green -
Threshold
Remote Input
9
No acon required; sensor is ready for
Dynamic TEACH method
2. Enter Dynamic TEACH.
Method Acon Result
SET Buon Click the SET rocker buon Display: Flashes "dYn tch" then holds on
"1234 dYn"
Remote Input Single-pulse remote input
3. Present ON and OFF Condions.
Method Acon Result
SET Buon Present ON and OFF condions Display: Red - Signal Level; Green -
Threshold
Remote Input Present ON and OFF condions
8
SET Buon: 0.04 seconds ≤ "Click" ≤ 0.8 seconds
9
Remote Input: 0.04 seconds ≤ T ≤ 0.8 seconds
DF-G3 Long Range Expert
™
Dual Display Fiber Amplier
18 www.bannerengineering.com - Tel: 763.544.3164