Remember: Manual adjustments are disabled when Auto Thresholds are ON
Follow these steps to perform a Dark SET:
Note: TEACH Selecon must be programmed to dr SEt.
1. Enter Adjust Mode.
Method Acon Result
SET Buon
17
Set Mode switch to ADJ Display: Red - Signal Level; Green -
Threshold
Remote Input
18
No acon required; sensor is ready for Dark
SET method
2. SET Sensing Condion.
Method Acon Result
SET Buon • Present sensing condion
• Click the SET rocker buon
Threshold Condion Accepted Displays
read "dr SEt" then alternate "PASS" with %
Oset
19
; Sensor returns to Adjust mode
Threshold Condion Not Accepted
Displays read "dr SEt" then alternate
"FAIL" with minimum % Oset
19
for
sensing condion; Sensor returns to Adjust
mode
Remote Input • Present sensing condion
• Single-pulse the remote input
3. Return to RUN Mode.
Method Acon Result
SET Buon Move Mode switch to RUN Display: Red - Signal Level; Green -
Threshold
Remote Input No acon required; sensor returns to RUN
mode automacally
3.5.6 Calibraon SET
•
Sets a threshold exactly at the presented condion
• Threshold can be adjusted using "+" and "-" rocker buon (Manual Adjust)
A single sensing condion is presented, and the sensor posions a threshold exactly at the presented condion. When a condion
lighter than the threshold is sensed, the output either turns ON or OFF, depending on the LO/DO seng.
17
SET Buon: 0.04 seconds ≤ "Click" ≤ 0.8 seconds
18
Remote Input: 0.04 seconds ≤ T ≤ 0.8 seconds
19
See Troubleshoong on page 25 for more explanaon of the % Oset displayed aer the Dark SET method
DF-G3 Long Range Expert
™
Dual Display Fiber Amplier
www.bannerengineering.com - Tel: 763.544.3164 23