Method Acon Result
SET Buon
5
Set the Mode switch to ADJ. Display: Red - Signal Level; Green -
Threshold
Remote Input
6
No acon is required; sensor is ready for
the Two-Point TEACH method
2. Teach the
rst condion.
Method Acon Result
SET Buon
a. Present the rst
condion.
b. Click the SET rocker buon.
Display: Flashes "2Pt tch" then holds on
"1234 2nd"
Remote Input
a. Present the rst
condion.
b. Single-pulse the remote input.
T
3. Teach the second condion.
Method Acon Result
SET Buon
a. Present the second condion.
b. Click the SET rocker buon.
TEACH Accepted
Displays alternate "PASS" and % Minimum
Dierence
7
; Sensor returns to Adjust
mode
TEACH Not Accepted
Displays alternate "FAIL" and % Minimum
Dierence
7
; Sensor returns to Adjust
mode
Remote Input
a. Present the second condion.
b. Single-pulse the remote input.
T
4. Return to Run mode.
Method Acon Result
SET Buon Move the Mode switch to RUN Display: Red - Signal Level; Green -
Threshold
Remote Input No acon is required; sensor returns to
RUN mode automacally
3.5.2 Dynamic TEACH
Teaches
on-the-y
Establishes a single switching threshold
Threshold can be adjusted using "+" and "-" rocker buon (Manual Adjust)
Dynamic TEACH is best used when a machine or process may not be stopped for teaching. The sensor learns during actual sensing
condions, taking mulple samples of the light and dark condions and automacally
seng the threshold at the opmum level.
5
SET Buon: 0.04 seconds "Click" 0.8 seconds
6
Remote Input: 0.04 seconds T 0.8 seconds
7
See Troubleshoong on page 25 for more explanaon of the % Minimum Dierence displayed aer the Two-Point TEACH method.
DF-G3 Long Range Expert
Dual Display Fiber Amplier
www.bannerengineering.com - Tel: 763.544.3164 17