Functional Description
3-16
Default Settings
BE3-GPR default settings when displayed using the S command.
OV = 1, 140, 130, 0
UV = 1, 100, 110, 0
OF = 1, 610, 605, 0
UF1 = 1, 590, 595, 0
UF2 = 1, 580, 585, 0
NGF = 1, 25, 20, 0 (NGF version)
OC = 1, 100, 90, 17, 10, 0 (TOC version)
PHBAL = 0, 10, 5, 1
REVPWR = 0, 100, 50, 0
REACTI = 0, 20, 15, 0
SYNC = 0, 1, 1, 2, 1, 1, 2
DBUS = 0, 10
CFG = 1, 5, 1
Default settings interpreted in the order displayed.
OV = Over Voltage Enabled Trip=140v Reset=130v TD=0s
UV = Under Voltage Enabled Trip=100v Reset=110v TD=0s
OF = Over Frequency Enabled Trip=61.0Hz Reset=60.5Hz TD=0s
UF1 = Under Frequency 1 Enabled Trip=59.0Hz Reset=59.5Hz TD=0s
UF2 = Under Frequency 2 Enabled Trip=58.0Hz Reset=58.5Hz TD=0s
NGF = Neutral Gnd Fault I Enabled Trip=0.25A Reset=0.20A TD=0s
(NGF version)
OC = Overcurrent Enabled Trip=1.00A Reset=0.90A TD=1s
(TOC version) Curve = 17 Voltage Restraint = 0
PHBAL = Phase Balance Disabled Trip=10v Reset=5v TD=1s
REVPWR = Reverse Power Disabled Trip=100w Reset=50v TD=0s
REACTI = Reactive I Disabled Trip=0.20A Reset=0.15A TD=0s
SYNC = Sync Disabled Fast=1 Delta V=1v Delta Ph=2
°
Window=1 Delta F=0.1Hz TD=0.2s
DBUS = Dead Bus Disabled Trip=10v
CFG = Configuration Auto Reset 5A CT’s Single Phase Sensing
Optional Communications Software
Basler Electric offers a Windows
software package that Enhances communications to BE3-GPRs. This
software package also provides a real time metering capability for monitoring generator voltage,
frequency, current, watts, power factor, and volt-amperes. BE3-GPR Windows
interface software
serves two primary functions. One, it provides a user friendly environment to change or make relay
settings. Without the software, you must be familiar with the BE3-GPR terminal commands to program
relay settings. With the software, on-screen displays guide you through the setting process. Two, the
software provides a means to monitor the metering results through the communications interface.
Metered data is displayed on the computer screen and refreshed approximately every second. Real time
monitoring provides critical generator data for evaluating system performance. The interface software
also allows the user to save setup configurations to a disk. This allows a user to save multiple setups for
later use and saves setup time when configuring multiple units. Please contact your sales representative
or the Customer Service Department, Power Systems Group, Basler Electric, Highland, Illinois.