Installation
4-9
Figure 4-10. BE3-GPR (NGF) P-2 With Single-Phase, Line-to-Line Sensing and Conditioning,
and 5A CTs.
2
1
IT IS IMPERATIVE THAT THIS INPUT BE
PROPERLY CONNECTED IN RELATIONSHIP
WITH TERMINALS 1 AND 3.
NOTES:
INPUT IS NOT REQUIRED IF SYNC-CHECK
IS NOT PRESENT.
3534332624 32312291113 + 20-73
3736 38 39 40 41 42 43 51504948474644 45 59585756555452 53 67666564636260 61 68 69 70
D2225-02
01-31-00
OV
NGF
PH
WDT REV
REACT
SYNC
PROGRAM
ENABLE
OUTPUT
DISABLE
SAFE
ENABLE
BUS
GEN
A
B
C
TRIP
RESET
NGF
CT
ØB CT
TO BUS
BREAKER
CLOSE
CIRCUIT
TO
TRIP
CIRCUITS
TO
GPR
FAIL
CIRCUIT
TO TRIP CIRCUITS
1
2
3
12 VDC
OR
24 VDC
-+
BE3-GPR
UV OF UF1 UF2
BAL
CHECKCURFAIL PWR
24681012
FAIL
1
3
TERMINAL 35 IS COMMON FOR BOTH PHASE AND
NEUTRAL GROUND FAULT CT CONNECTIONS. FOR
5A CTS, PHASE CTS CONNECT TO TERMINAL 31,
AND NEUTRAL GROUND FAULT CTS CONNECT TO
TERMINAL 33. BOTH CT CONNECTIONS MUST USE
THE SAME QUANTITY (5A OR 1A).
1
ØB
ØA
ØB
ØA