Syscompact 2000 M pro Cable fault pre-location
822-175-2 67 / 98
5. Depending on the intended output voltage, select a voltage range:
Voltage range 0 8 kV: Select the symbol (parallel connection).
With parallel connection, at 8 kV you receive the max. surge energy of 1024 J in the
surge voltage range.
Voltage range 0 16 kV: Select the symbol (series connection).
With series connection, at 16 kV you receive the max. surge energy of 1024 J in the
surge voltage range.
6. Press the ENTER key.
The parameters are saved.
12.5.3 Performing ICM measurements
Prerequisites
The test area is secured.
The test object is connected properly.
Further information: Chapter Commissioning (on page 33)
The anticipated fault distance is > 150 m.
The IRG 2000 is connected to the system via the ICM port.
The general pre-location parameters and the ICM parameters have been set.
Further information: Chapter Setting the general pre-location parameters on the IRG 2000
(on page 52), chapter Setting ICM parameters (on page 66)
Procedure
1 System control panel
2 IRG 2000 time domain reflectometer
On the system control panel
1. Press the MENU key on the display.
2. Select the SURGE MODE menu item and press the ENTER key.
3. Release the high voltage: Press the key for at least one second.
The system status changes to the Ready to switch on operating state. The red indicator
light flashes for approx. 6 seconds.
4. Switch on the high voltage by pressing the key within 6 seconds (while the red
indicator light flashes).
The system status changes to the In operation operating state. The set parameters appear
on the display.