Tab.44 Menu W
Wireless
Parameter
number
Parameter Description
120 B
Activation of wireless connection with the base unit.
121 T
The test mode is used to check the wireless communication.
130 R
Checking the link.
131 R
Checking the link.
132 R
Checking the link.
133 O
Outside temperature
sensor
Checking the link.
134 R
Checking the link.
135 I
Checking the link.
140 D
Deletes all appliances
Tab.45 Menus T
– T
– T
Temps / mode CH3
Parameter number Parameter Description Unit Factory set
ting
Heating
circuit 1
Heating
circuit 2
Heating
circuit 3
714 1014 1314 F
Frost protection
setpoint
°C 6
720 1020 1320 H
Heating curve gradient: The regulator calcu
lates the flow T° set point which is used for the
control system, according to outside weather
conditions.
–
Heating
circuit 1:
1.5
Heating
circuit 2:
0.7
Heating
circuit 3:
0.7
730 1030 1330 S
Summer/winter
heating limit
Limit temperature for Heating/Frost Protection
Mode switching. Triggers or shuts down the
heating in the course of the year according to
variations in outside T°. This switch is made
automatically in Automatic mode.
20
732 1032 1332 2
The heating is shut down when the outside T°
is equal to the room temperature + parameter
732 (deactivated in Comfort mode).
°C 0
740 1040 1340 F
The flow set point calculated is limited by the
set value.
°C 25
741 1041 1341 F
The flow set point calculated is limited by the
set value.
°C 80
742 1042 1342 F
Flow temp
setpoint room stat
The set flow value is applied in room tempera
ture thermostat mode. ‘ ---‘ the boiler is running
in modulation mode.
°C 80
746 1046 1346 D
750 1050 1350 R
Influence of the room T° and the outside T°
on calculating the flow temperature: ---%:
Simple regulation in accordance with outside
weather conditions
1…99%: Regulation in accordance with out
side weather conditions with room tempera
ture influence.
100%: Regulation in accordance with the
room temperature only.
%50
9 Settings
7609474 - v02 - 04092014 75