P
Parameter number Parameter Description Unit Factory set
ting
Heating
circuit 1
Heating
circuit 2
Heating
circuit 3
760 1060 1360 R
Room temp
limitation
Cuts the heating circulation pump if the room T
° exceeds the current set point + parameter
760, 1060, 1360
°C 0
0.5
809 1109 1409 C
Continuous pump
operation
No
: The heating circuit / boiler pump may be
shut down during an accelerated decline in
temperature or when the room temperature
set point is reached.
Yes
: The heating circuit / boiler pump also
continues to run during the accelerated de
cline in temperature and when the room tem
perature set point is reached.
–no
834 1134 1434 A
Actuator running
time
Setting the stroke of the servomotor on the
mixing valve used
seconds 30
850 1150 1450 F
Floor curing
function
Controlled screed-drying function:
Off
: The function is inoperative.
Curing/functional heating
: Active for 7 days,
3 days at a T° of 25°C and 4 days at a T° of
55°C
Curing heating
: Active for 18 days, 6 days
from 25°C to 55°C increasing by 5°C a day,
6 days at a T° of 55°C, 6 days from 55°C to
25°C diminishing by 5°C a day.
Functional/curing heating
: First, "Functional
Heating" cycle, and then, "Ready for Occu
pation".
Functional heating
: First, "Ready for Occu
pation" cycle, and then, "Functional Heating".
Manually
: Regulation is based on the "Man
ual Control Drying" set point.
SO
Off
851 1151 1451 F
Floor curing setp
manually
The flow temperature set point of the "Manual"
controlled drying function can be set separately
for each heating circuit.
°C 25
855 1155 1455 F
Floor curing setp
current
Displays the current day of the controlled
screed-drying function. With ‘ ---‘ the function is
deactivated.
- ‘---’
856 1156 1456 D
Days
complete.current
Displays the current flow temperature set point
of the controlled screed-drying function. With
‘ ---‘ the function is deactivated.
- ‘---’
Tab.46 Menu T
Temps / mode hot water
Parameter
number
Parameter Description Factory setting
1600 O
Operating mode Off
Permanent running on the antifreeze set point
On
DHW loading is done automatically at the nominal set point
Eco
The temperature maintenance function is deactivated
On
1610 H
Hot water temp
setpoint
DHW set point during release times 6
60°C
1612 R
Reduced temp
setpoint
Reduced set point outside release times 3
35°C
1620 R
Release
Start-up enabled:
Time hot water
: This setting provides DHW preparation with a
dedicated timer program.
Time setting central heating
: The release of DHW is done in //
of the period of occupation of the heating circuits.
24h/day
: Default setting for instantaneous boilers.
Time hot water
9 Settings
76 7609474 - v02 - 04092014

Table of Contents

Other manuals for Baxi POWER HT+ Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Baxi POWER HT+ Series and is the answer not in the manual?

Baxi POWER HT+ Series Specifications

General IconGeneral
ModelPOWER HT+ Series
CategoryBoiler
Installation TypeWall-mounted
Heat Exchanger MaterialStainless Steel
Warranty2 years
Fuel TypeNatural Gas
Control SystemIntegrated Control
Ignition TypeElectronic

Related product manuals