6. Select the Y
parameter by turning the button.
7. Confirm the parameter selection by pressing the
button.
Press the
MENU
key to return to the main screen.
The reset of the timer program to zero has been successful.
9.2.14 Setting a temporary heating flow temperature
1. From the control panel main screen, turn the button to increase
or reduce the temperature value.
2. Confirm the menu selection by pressing the button
.
9.2.15 Managing boilers in cascade
Boilers in cascade are controlled and managed by the lead boiler.
1. Set the following parameters on the lead boiler:
Tab.59 Configuration lead cascade boiler
Parameter num
ber
Parameter Setting Description
3540 Auto source seq ch'over Number of hours Operating time before the auto
matic change of the lead boiler
sequence.
3541 A
Auto source seq exclusion
First
First and last
Last
None
Exclusion of the boiler or boilers
from the periodic sequence rota
tion.
List of installer parameters, page 74.