3.2 Characteristic data of device
3.2.1 Basic modules
3.2.1.1 SMX10/10A/10R/10AR (/2, /4x, /x
(1)
)
Type designation
Device design
Design of module with the following periphery:
14 Digital inputs
2 Pulse outputs
2 Relay outputs (6x SMX10R, SMX10AR)
2/4 pn- or pp- switching outputs
2 Auxiliary outputs
2 Analog inputs (SMX10A, SMX10AR)
1 diagnostic- and configuration interface
1 function button
1 7-segment display
1 status-LED
14 status LEDs for inputs
2 status-LEDs for pulse outputs
2 status-LEDs für relay outputs
6 status LEDs for outputs
1 Optional: Communication interface(/4x, 5x, /x
(1)
)
Characteristics of the module:
Extendable to:
o max. 42 safe digital inputs,
o max. 12 safe digital outputs,
o max. 20 sichere digitale I/O’s,
o max. 11 safe relay outputs,
o max. 10 auxiliary outputs
Logic processing up to Pl e acc. to EN ISO 13849-1 or SIL 3 acc. to IEC 61508
Freely programmable Modular controller for up to 800 IL instructions
Logic diagram oriented programming
Pulse outputs for cross-shorting detection of digital input signals
External contact monitoring of connected switchgear (EMU)
Monitored relay outputs for safety relevant functions
Switchable safe semi-conductor outputs pn-, pp- switching for safety-relevant functions
Parameter management for expansion modules in base device
Comprehensive diagnostics functions integrated
Coded status display via front-side 7 segment display and status LEDs
Multifunction buttons (quit, start, reset) can be operated from the front side
Optional: Communication interface