EasyManua.ls Logo

BBH SMX 12-2 - Mechanical data

Default Icon
234 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation manual
HB-37350-810-01-51F-EN SMX Installation manual.docx Page 44 of 234
Version: 50F
06 10
Temperature rating
30°C
24 VDC; 2A (G.P.)
Temperature rating
50°C
24 VDC; 1,8A (G.P.)
Max. total current (I/O)
10A
Rated data
relays
Normally open
24 VDC; 2A (Pilot Duty)
120 VAC; 2A (Pilot Duty)
Normally closed
(Read back contact)
24 VDC; 2A (Pilot Duty)
Environmental data
Temperature
0°C … +50°C operation
-25C° … +70C° storage and transport
Class of protection
IP 20
Climatic category
3k3 acc. to DIN 60 721-3
Min-, Maximum relative humidity (no condensation)
5% - 85%
EMC
EN 61000-6-2, EN 61000-6-4, EN 61000-6-7, EN
61800-3, EN 61326-3, EN 62061
Operating altitude
2000m
Overvoltage category
III
Degree of pollution
2
Mechanical data
Dimensions (HxDxW [mm])
SMX32-0/2/D = 100x115x67,5
SMX32-0R/2/D = 100x115x90
SMX32-1/2/D = 100x115x90
SMX32-1R/2/D = 100x115x112,5
Weight (g)
SMX32-0/2/D = 400
SMX32-0R/2/D = 520
SMX32-1/2/D = 500
SMX32-1R/2/D = 620
Mounting
To snap on top-hat rail
Number of T-bus
SMX32-0/2/D
3
SMX32-0R/2/D
4
SMX32-1/2/D
4
SMX32-1R/2/D
5
Min. terminal cross-section / AWG
0,2 mm² / 24
Max. terminal cross-section / AWG
2,5 mm² / 12
(**) pn/pp are configurable via SafePLC2
(***) Derating, see Chapter „Derating outputs
1)
Value applies only for extension module. For a total assessment in accordance with EN ISO 13849-1 one must
use a sries connection with the corresponding basic device
=> PFH
Logic
= PFH
Basic
+ PFH
Extension

Table of Contents