Installation manual
HB-37350-810-01-51F-EN SMX Installation manual.docx Page 89 of 234
Version: 50F
Safety note:
Not recommended for safety applications! In this context see also the notes in EN ISO
13849-1 concerning the application and the required fault exclusions.
4.3.4.2.2 Single-channel switching relay or semi-conductor output with external switching
amplifier and testing
When using external switching amplifiers or downstream electro-mechanical, pneumatic or
hydraulic components, the setup for testing the complete chain and a message/warning feature
for detected faults is required in order to achieve PI c or higher.
Positively guided auxiliary contacts are especially needed for electro-mechanical devices and
message contacts for the valve position are required for hydraulic or pneumatic components.
The message/warning device must ensure that the operator recognizes the dangerous situation
immediately.
The achievable PI is mainly depending on the test rate, PI d acc. to nach EN ISO 13849-1 can
maximally be achieved!
Q1_PP
X21
X12
Q2_PN
Q3_PP
Q4_PN
NC
NC
Y1
Y2
X13
I13
I14
T1
T2
L +
L -
Fig.: Single-channel relay output with testing
Safety note:
Only conditionally recommended for safety applications! In this context see also the notes
in EN ISO 13849-1 concerning the application and the required fault exclusions.
For PI c or higher a test rate of > 100 * the request rate is required.
For PL c and higher a message/warning feature is required, which informs the operator
immediately about a dangerous situation