EasyManua.ls Logo

BEAMEX FB150 - Page 65

Default Icon
78 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
59
Digital communication interface
Serial Commands - Alphabetic Listing
SOUR:PROT:TRIP?
Read the temperature cutout tripped state. Range = {0, 1}; 0 = No Cutout; 1 = Cutout
Example: SOUR:PROT:TRIP?
Response: 0
A value of 0 is returned if the cutout set point has not been reached. Otherwise a value
of 1 is returned and the cutout set point has been reached.
SOUR:RATE[?] [n]
Read or set the control temperature rate of change (Scan Rate), °C or °F per minute.
Min: 0.10, Max: 500.00; Default: 100.00
Read Example: SOUR:RATE?
Response: 0.531
Set Example: SOUR:RATE 1.26
The response to this command starts out high initially and decreases as the set point is
reached.
SOUR:SENS:CAL:GRAD<x>[?] [n]
NOTE: This command is unconditionally protected and requires a password to
set it.
Read or set the axial gradient control parameter, where “x” is a numeric value indicat-
ing the parameter. [1] = GRAD1 = GRAD 1, [2] = GRAD2 = GRAD 2, [3] = GRAD3
= GRAD 3, [4] = GRAD4 = GRAD 4, [5] = GRAD5 = GRAD 5. “n” is a real number
ranging from -1.0 to 1.0 entered as a ratio of the main heater power
Read Example: SOUR:SENS:CAL:GRAD2?
Response: 0.05
Set Example: SOUR:SENS:CAL:GRAD2 0.08
The top zone heater reacts as a ratio of the mains heater power to control the axial
gradient.
SOUR:SENS:CAL:PAR<x>[?] [n]
NOTE: This command is unconditionally protected and requires a password to
set it.
Read or set a control temperature calibration parameter, where “x” is a numeric value
indicating the parameter. [1] = PAR1=Temp 1,PAR2=Temp 2, PAR3=Temp 3. “n” is
the entered value of the parameter. Range = ±50.00; Defaults: 0.000

Table of Contents

Related product manuals