X2 series with embedded CODESYS control Recommendations and limitations
SUEN00392E 2022-03
33 (61)
Normal.dotm
, 2020-09-09
Output status in STOP mode
It is always recommended to set all outputs to FALSE in STOP mode in order to prevent a dangerous
situation. This is done by setting the Update IO while in STOP mode parameter.
The communication driver will then follow the state of the application and STOP communicating
when stopping the program execution, this will trigger a watchdog event in the slaves and will take the
action required depending of the type of application.