Operation and setting
50
IRDH275_D00122_02_M_XXEN/10.2016
6.4 Menu ISO SETUP: Setting of the basic ISOMETER®
functions
All alarm functions such as Alarm 1 and Alarm 2 (prewarning and main alarm),
the operating principle of the alarm relays K1 and K2 (N.O = N/O operation,
N.C = N/C operation), the fault storage behaviour and a selection of two cur-
rent output ranges are set in this menu.
6.4.1 Response values Alarm 1 and Alarm 2
The response values Alarm 1 and Alarm 2 are selected with the UP/DOWN
keys and stored with the ENTER key.
6.4.2 Operating principle of the alarm relays
K1/K2 are factory set to N.O Test, that means N/O operation. When the supple-
ment "Test" has been selected, the alarm relays switch over during a manual
self test.
If, for any reason, the alarm relays may not switch over during a manual self
test, the settings N.C or N.O are to be selected.