8. Technical data IRDH275(B)
8.1 Data in tabular form
The values marked with * are absolute values
Insulation coordination acc. to IEC 60664-1
Rated voltage.....................................................................................................................................................AC 800 V
Rated impulse voltage/pollution degree............................................................................................................8 kV / 3
Voltage ranges
IRDH275....:
Nominal voltage range U
n
..................................................................................................1AC / 3 (N) AC 0…793 V*
Nominal frequency f
n
(for f < 50 Hz see characteristic curve on page 79) ............................................ 0,1…460 Hz
Nominal voltage range U
n
...................................................................................................................... DC 0…650 V*
IRDH275….-435:
Supply voltage U
s
(see nameplate).......................................................................................................AC 88…264 V*
Frequency range U
s
................................................................................................................................... 42…460 Hz
Supply voltage U
s
(see nameplate)...................................................................................................... DC 77…286 V*
IRDH….-427:
Supply voltage U
s
(see nameplate)..................................................................................................... DC 19.2…72 V*
IRDH275….:
Power consumption .......................................................................................................................................... ≤ 14 VA
Response values
Response value R
an1
(Alarm 1) ................................................................................................................1 kΩ…10 MΩ
Response value R
an2
(Alarm 2) ................................................................................................................1 kΩ…10 MΩ
Relative uncertainty (20 kΩ…1 MΩ) (acc. to IEC 61557-8:2007-01) ............................................................. ±15 %
Relative uncertainty (1 kΩ…20 kΩ)....................................................................................................+2 kΩ / +20 %
Relative uncertainty (1 MΩ…10 MΩ).............................................................................................. 0,2 MΩ / +20 %
Response time t
an
at R
F
= 0.5 x R
an
and C
e
= 1 μF.............................................................................................. 5 s
Measuring time.......................................................................................................................... see characteristic curve
Hysteresis (1 kΩ…10 kΩ) ................................................................................................................................... +2 kΩ
Hysteresis (10 kΩ…10 MΩ)................................................................................................................................. 25 %

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender ISOMETER IRDH275 and is the answer not in the manual?

Bender ISOMETER IRDH275 Specifications

General IconGeneral
BrandBender
ModelISOMETER IRDH275
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals