EasyManua.ls Logo

Bender ISOMETER IRDH275 - Technical Data IRDH275(B); Data in Tabular Form

Bender ISOMETER IRDH275
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
73
IRDH275_D00122_02_M_XXEN/10.2016
8. Technical data IRDH275(B)
8.1 Data in tabular form
The values marked with * are absolute values
Insulation coordination acc. to IEC 60664-1
Rated voltage.....................................................................................................................................................AC 800 V
Rated impulse voltage/pollution degree............................................................................................................8 kV / 3
Voltage ranges
IRDH275....:
Nominal voltage range U
n
..................................................................................................1AC / 3 (N) AC 0…793 V*
Nominal frequency f
n
(for f < 50 Hz see characteristic curve on page 79) ............................................ 0,1…460 Hz
Nominal voltage range U
n
...................................................................................................................... DC 0…650 V*
IRDH275….-435:
Supply voltage U
s
(see nameplate).......................................................................................................AC 88…264 V*
Frequency range U
s
................................................................................................................................... 42…460 Hz
Supply voltage U
s
(see nameplate)...................................................................................................... DC 77…286 V*
IRDH….-427:
Supply voltage U
s
(see nameplate)..................................................................................................... DC 19.2…72 V*
IRDH275….:
Power consumption .......................................................................................................................................... ≤ 14 VA
Response values
Response value R
an1
(Alarm 1) ................................................................................................................1 kΩ…10 MΩ
Response value R
an2
(Alarm 2) ................................................................................................................1 kΩ…10 MΩ
Relative uncertainty (20 kΩ…1 MΩ) (acc. to IEC 61557-8:2007-01) ............................................................. ±15 %
Relative uncertainty (1 kΩ…20 kΩ)....................................................................................................+2 kΩ / +20 %
Relative uncertainty (1 MΩ…10 MΩ).............................................................................................. 0,2 MΩ / +20 %
Response time t
an
at R
F
= 0.5 x R
an
and C
e
= 1 μF.............................................................................................. 5 s
Measuring time.......................................................................................................................... see characteristic curve
Hysteresis (1 kΩ…10 kΩ) ................................................................................................................................... +2 kΩ
Hysteresis (10 kΩ…10 MΩ)................................................................................................................................. 25 %

Table of Contents

Related product manuals