Operation and setting
64
IRDH275_D00122_02_M_XXEN/10.2016
6.9 Menu SERVICE
This menu item is provided for the Bender service personnel and is protected
by a password against erroneous settings. It is intended to provide fast fault
clearance by qualified experts in the event of a device error.
6.10 Parameterization via Internet
The parameters of an IRDH275B indicated below can be checked and set from
a remote place of use by using a personal computer. In addition, a browser
(viewing program for Internet application) and the BMS-Ethernet-Gateway
COM460 are required.
Remote setting is possible for:
• Response value Alarm 1 (1…10,000 kΩ) (Y1)
• Response value Alarm 2 (1…10,000 kΩ) (Y2)
• Operating principle alarm relay 1 (e.g. N/O operation)
• Operating principle alarm relay 2 (e.g. N/O operation)
• Measuring principle (AMP or DC)
• Current output ranges for external measuring instruments
(0/4…20 mA)
• Maximum system leakage capacitance (150 μF or 500 μF)
• Time for repetition of the automatic self test (off/ 1 h/ 24 h
• Starting time of the automatic self test (0.00…23.00 h)
• Language of the alarm messages to be displayed (D, GB)
• Setting the fault memory to ON or OFF